Description
The
HU-224/225 is an extremely fast, stable and accurate humidity
transducer designed for harsh environments. The polymer
capacitance sensor is not affected by harsh contaminants,
condensation, fog or extremely high humidity over a prolonged
period of time. If dust or other contaminants accumulate
on the
sensor, the probe can be washed in industrial grade isopropyl
alcohol and put back in service without any calibration
shift. Each unit is individually calibrated in an environmental
test chamber to meet or exceed NIST traceable ±2%
or ±3%
accuracies. The HU-224/225 is temperature compensated for
-30°F to
-130°F operation with negligible error. For space humidity,
an aesthetically appealing ABS enclosure which may be flush
mounted or fits a standard 2" x 4" handy box is
available and for duct humidity applications, a rugged NEMA-4
(IP-65) steel enclosure with external mounting bracket is
also available. Two enclosure types, field selectable outputs,
fully temperature compensated NIST traceable accuracy, non-interacting
zero and span adjustments, short circuit and reverse polarity
protected output, and a liberal two year warranty are some
of the features which make the HU-224/225 the industry's
highest performance, most reliable humidity transducer.
The
HU-224/225 incorporates a bulk polymer capacitive ultra-fast
sensing element which is immune to most contaminants and
at the same time provides a stable, repeatable, and accurate
humidity measurement with negligible hysteresis. The sensing
element is not affected by condensation. In fact, it may
be immersed in distilled water without degrading the calibration
accuracy. The HU-224/225 utilizes sophisticated integrated
circuits to provide a high level, fully conditioned, and
temperature-compensated output.
On
VDC output units, two additional field selectable options
are available: dual outputs 0 to 5 or 0 to 10 VDC, and
dual unregulated supply voltages 12 to 35 VAC or 12 to
40 VDC. By
merely moving
a shorting plug, one can select the desired output for
the specific application. As far as supply voltage is concerned,
the unit automatically configures for AC or DC and no field
selection is necessary. Another feature is that the output
is fully protected from short circuit to ground, or if
the supply voltage is applied by mistake to the output.
Past experience demonstrates that field related wiring
problems do occur. Instead of denying this fact, this protection
circuit is designed in to ensure trouble-free start-up.
The VDC output unit is also designed to handle low impedance
circuits. In fact, the unit can drive up to 1K ohm minimum.
In this way, multiple controllers, indicators, or other
devices can be paralleled to the output without performance
degradation.
The
mA output units can function over a wide unregulated supply
voltage range: 12 to 40 VDC without any affect on calibration
or performance. The unit has reverse polarity protection
built in. As a result, it is next to impossible to damage
the unit by mis-wiring. By using sophisticated low drop-out
voltage regulators and CMOS integrated circuits, the mA
output unit can drive very high output impedance. In fact,
with only 12 VDC supply, the unit can drive 400 ohms. At
40 VDC, the unit is capable of handling up to 3000 ohms
load. In this way, the output loop can be tied in series
to multiple controllers, indicators, and other devices
without degrading the performance.
NIST
traceable humidity standards are utilized to calibrate
and certify the HU-224/225.
Calibration data on each unit is archived digitally for
SPC and QC purposes. All automated calibration systems
are networked and data is available online to numerous
individuals at the same time. In this way, extremely
high standards of quality and calibration integrity are
maintained.
The
HU-224/225 incorporates a rugged NEMA-4 (IP-65) fully
gasketed, dustproof and splashproof enclosure for monitoring
duct humidity or an aesthetically appealing ABS plastic
wall mount enclosure for monitoring space humidity. The
enclosure has an external mounting bracket to facilitate
field installation. A ½" (.875"/22.25
mm diameter) knock-out for conduit connection is also provided.
A liquid
tight cable connector is also supplied if the unit is not
being hard wired. Once installed, the enclosure maintains
its environmental rating and protects the electronics and
the sensing element from condensation, corrosive contaminants
and other environmental pollutants. The wall mount enclosure
may be flush mounted on any flat surface or fits a standard
2" x 4" handy box. Louvers are provided on the
top and bottom of the enclosure to ensure ample air flow
for fast response. Both enclosure options also have additional
features for ease of installation including unpluggable
terminal block, easily accessible zero and span trimmers,
and conveniently located shorting plugs for field selection. |